INTERFACE C MEDIUM VOLTAGE SYMMETRICAL SEPARABLE CONNECTORS CATALOGUE 2017
NEXANS NETWORK SOLUTIONS DIV. EUROMOLD
COMPANY PRESENTATION
EUROMOLD
Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium voltage energy distribution. Euromold provides a complete range of accessories for underground cables: premoulded EPDM rubber connectors for cables and epoxy bushings for transformers and switchgear, as well as a large range of coldshrinkable terminations and joints from 12 to 42 kV. Euromold is also the manufacturer of electrical components for the high voltage accessories of the Nexans group.
International standards
All our products meet the International standards like CENELEC HD 629.1, CENELEC EN 50180, IEC 60137, IEC 60502-4… or country specifications. Official certificates, CESI, KEMA, ATEX… prove the conformity of our products. Long duration tests of existing or new products are continuously performed in our test fields.
Laboratory accreditation
Since June 2000, Euromold’s independent ELAB laboratory obtained the BELAC accreditation no.144-TEST conform with the European standards for laboratories ISO 17025 for electrical testing of low and medium voltage cable accessories according to the international standards EN 50393, IEC 605024, IEC 61442 and HD 629.
ISO 9001 Certificate
Since 1992, Euromold’s commitment to quality is demonstrated by its ISO 9001 certification.
While every care is taken to ensure that the information contained in this publication is correct, no legal responsibility can be accepted for any inaccuracy. Nexans Network Solutions N.V. - Div. Euromold reserves the right to alter or modify the characteristics of its products described in this catalogue as standards and technology evolve.
SYMMETRICAL SEPARABLE CONNECTORS INTERFACE C
TABLE OF CONTENTS
INTERFACE C1 & C2
480TB - tee connector 400LB - elbow connector 400TB - tee connector 440TB - tee connector 440PB - coupling connector 400PB - XSA - surge arrester 400TR and 400TR-LB - test rods 400TK and 400SW installation tools Accessories Possible arrangements
Dimensions according to European CENELEC EN 50180 and 50181 (in mm).
Dia. 56±0.2 Dia. 46±0.2 Dia. 22 min for C1 Dia. 32 nominal for C2 M16 x 2 - 6H
0
1.5 -0.5
29 min.
90±0.2
11 min.
Dia. 70±0.2
2
In mm.
05/2017
CONNECTING POSSIBILITIES BUSHINGS / ACCESSORIES
CONNECTION
Equipment interface
dead-ending of equipment
CONNECTORS / ACCESSORIES
(K)(M)400DR-B
Dead-end receptacle
(K)(M)400AR-3
Equipment bushing
(K)(M)400AR-4
Equipment bushing
(K)(M)400AR-5
cable to equipment
Equipment bushing
(K)400LB/G
Elbow connector
(K)(M)400AR-6
Equipment bushing
(K)(M)400SFR-B
(K)(M)440PB/G
Equipment bushing
(K)(M)(P)400TB/G
Coupling connector
Tee connector
400A-24B
In-air bushing
(K)(M)400SOP-B
cable isolation
400GP-B
cable earthing
Stand-off plug
(K)(M)(P)440TB/G Tee connector
400PB-XSA
Surge arrester
Earthing plug
(K)400RTPA
tap-off 630/250A
Reducing tap plug
(K)(M)400CP-SC
in-line junction
Connecting plug
(K)(M)440CP
in-line junction
Connecting plug
For information on bushings please refer to our bushing catalogue.
3
05/2017
400LB
INTERFACE C ELBOW CONNECTOR
APPLICATION
TECHNICAL CHARACTERISTICS
Separable elbow connector designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors...). Also connects cable to cable, using the appropriate mating part.
• The thick conductive EPDM jacket provides a total safe to touch screen which ensures safety for personnel. • Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.
DESIGN
205 mm
Separable connector comprising: 1. Conductive EPDM insert. 2. Conductive EPDM jacket. 3. Insulating EPDM layer moulded between the insert and the jacket. 4. Type C - 630 A interface as described by CENELEC EN 50180 and 50181. 5. Conductor connector (not included in the standard kit). 6. Insulating plug. 7. Cable reducer. 8. Earthing lead. 9. Transition contact M10/M16.
9 4
6
6/10 (12) kV 6.35/11 (12) kV 8.7/15 (17.5) kV 12/20 (24) kV 12.7/22 (24) kV
5
Up to 24 kV - 630 A
1 2
330 mm
8
The screen break design enables cable outer sheath testing without removing or dismantling the connector.
3
7
SPECIFICATIONS AND STANDARDS The 400LB separable connector meets the requirements of CENELEC HD 629.1.
Separable connector type
Voltage Um (kV)
Current Ir (A)
400LB/G K400LB/G
12 24
630 630
Conductor sizes (mm2) min
max
25 25
300 300 05/2017
4
KIT CONTENTS
The kit also comprises silicone grease, field control mastic and installation instructions.
The complete (K)400LB/G elbow connector kit comprises 3 x the following components:
3 x (K)400LB/G-W(-X) connector kit
Connector housing (K)400BLB
Transition contact + screw assembly 400LTS
ORDERING INSTRUCTIONS
Cable reducer 411CA-W
TABLE W
Select the part number which gives the best centring to the cable core insulation diameter. Add a 'K' for use up to 24 kV.
EXAMPLE: The copper wire screened cables are 24 kV, 240 mm2 stranded aluminium with a diameter over core insulation of 32.2 mm. Order 3 x K400LB/G-27 elbow connector kit.
Insulating plug 400LBP
Dia. over core insulation (mm)
Ordering part number 3 x 400LB/G-11 3 x 400LB/G-15 3 x 400LB/G-19 3 x 400LB/G-22 3 x 400LB/G-25 3 x 400LB/G-27
Dia. 10.2 or 13 10 max
Dia. 36 max 24 max
2 max
38 max
min
max
12.0 16.0 20.0 23.5 26.5 28.5
17.5 22.0 26.5 31.0 32.5 37.5
NOTES: We do not supply the compression lugs in the standard kit. All types of cable lugs can be used. The lugs must be within the dimensions specified and the palm of the lug must be copper or any equivalent alloy.
112 max 135 max
In mm.
For use with copper tape screened cables.
Order: Kit MT.
For use with Alupe or C 33-226 cables.
Please contact our representative.
For use with fabric tape (graphite) screened cables.
Order additional semi-conductive tape (type TSC).
Can be supplied with cable lugs.
For applications outdoors and in humid climate.
Components can be ordered individually.
Order: +MWS.
5
400TB
INTERFACE C TEE CONNECTOR
APPLICATION Separable tee shape connector (bolted type) designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors, ...). Also connects cable to cable when using the appropriate mating parts.
TECHNICAL CHARACTERISTICS • The thick conductive EPDM jacket provides a total safe to touch screen which ensures safety for personnel. • Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.
DESIGN Separable connector comprising: 1. Conductive EPDM insert. 2. Conductive EPDM jacket. 3. Insulating EPDM layer. 4. Type C - 630 A interface as described by CENELEC EN 50180 and 50181. 5. Conductor connector. 6. Basic insulating plug (with VD point). 7. Cable reducer. 8. Conductive rubber cap. 9. Clamping screw. 10. Earthing lead. The screen break design enables cable outer sheath testing without removing or dismantling the connector.
255 mm 220 mm
4
9
5
6
8
1 2 350 mm
6/10 (12) kV 6.35/11 (12) kV 8.7/15 (17.5) kV 12/20 (24) kV 12.7/22 (24) kV 18/30 (36) kV 19/33 (36) kV 20.8/36 (42) kV Up to 42 kV 630 A 800 A
3 10
7
SPECIFICATIONS AND STANDARDS The 400TB separable connector meets the requirements of CENELEC HD 629.1 S1.
6
Current Ir (A)
Separable connector type
Voltage Um (kV)
Current Ir (A)
When using a copper (-11-2) or a bolted (-14-5) conductor contact
400TB/G K400TB/G M400TB/G P400TB/G
12 24 36 42
630 630 630 630
800 800 800 800
Conductor sizes (mm2) min
max
35 35 35 35
300 300 240 240
05/2017
KIT CONTENTS The complete (K)(M)(P)400TB/G tee connector kit comprises the following components:
The kit also comprises silicone grease, field control mastic, installation instructions and crimp chart.
Conductor contact TMBC-X
Connector housing (K)(M)(P)400BT/G
Clamping screw 400TCS
ORDERING INSTRUCTIONS
Conductor contact TBC-X
(K)(M)(P)400TB/G-W-X connector kit
Basic insulating plug (K)(M)(P)400BIPA + rubber cap
Cable reducer 411CA-W
TABLE W
To order the tee connector, select the ordering part number which gives you the best centring of your core insulation diameter and substitute X using table X, according to your conductor size and type. Add a 'K' for use up to 24 kV, add an 'M' for use up to 36 kV, add a 'P' for use up to 42 kV.
Dia. over core insulation (mm)
Ordering part number 400TB/G-11-X 400TB/G-15-X 400TB/G-19-X 400TB/G-22-X 400TB/G-25-X 400TB/G-27-X
min
max
12.0 16.0 20.0 23.5 26.5 28.5
17.5 22.0 26.5 31.0 32.5 37.5
TABLE X
For use with copper tape screened cables.
Order: Kit MT.
For use with other cable types.
Please contact our representative.
For applications outdoors and in humid climate.
Order: +MWS.
Deep indent
35(K)M-10-2 50(K)M-10-2 70(K)M-10-2 95(K)M-10-2 120(K)M-10-2 150(K)M-10-2 185(K)M-10-2 240(K)M-10-2 300(K)M-10-2
35KM-10-1 50(K)M-10-1 70(K)M-10-1 95(K)M-10-1 120(K)M-10-1 150(K)M-10-1 185(K)M-10-1 240(K)M-10-1 –
For use in potentially explosive atmospheres (for 12 kV max).
Add -/ATEX to part number.
Copper conductor
Bolted
DIN hexagonal
Components can be ordered individually.
120.300-14-5
DIN hexagonal
Aluminium and copper conductor
95.240-14-5
35 50 70 95 120 150 185 240 300
Aluminium conductor
50.150-14-5
Conductor sizes (mm2)
16.95-14-5
EXAMPLE: The copper wire screened cable is 36 kV, 150 mm2 stranded copper with a diameter over core insulation of 32.5 mm. Order a M400TB/G-27-150(K) M-11-2 tee connector kit.
35(K)M-11-2 50(K)M-11-2 70(K)M-11-2 95(K)M-11-2 120(K)M-11-2 150(K)M-11-2 185(K)M-11-2 240(K)M-11-2 300(K)M-11-2
When installed on an appropriate equipment bushing:
800 A continuously
7
440TB
INTERFACE C TEE CONNECTOR
TECHNICAL CHARACTERISTICS
APPLICATION Separable tee shape connector (bolted type) designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors, ...). Also connects cable to cable when using the appropriate mating parts.
• The thick conductive EPDM jacket provides a total safe to touch screen which ensures safety for personnel. • Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.
DESIGN
Separable connector comprising: 1. Conductive EPDM insert. 2. Conductive EPDM jacket. 3. Insulating EPDM layer moulded between the insert and the jacket. 4. Type C - 630 A interface as described by CENELEC EN 50180 and 50181. 5. Conductor connector. 6. Basic insulating plug (with VD point). 7. Cable reducer. 8. Conductive rubber cap. 9. Clamping screw. 10. Earthing lead.
255 mm 220 mm
4
9 6
5
8
1 2 355 mm
The screen break design enables cable outer sheath testing without removing or dismantling the connector.
6/10 (12) kV 6.35/11 (12) kV 8.7/15 (17.5) kV 12/20 (24) kV 12.7/22 (24) kV 18/30 (36) kV 19/33 (36) kV 20.8/36 (42) kV Up to 42 kV 630 A 1250 A
3
10
7
SPECIFICATIONS AND STANDARDS The 440TB separable connector meets the requirements of CENELEC HD 629.1.
8
Separable connector type
Voltage Um (kV)
Current Ir (A)
Current Ir (A)
440TB/G K440TB/G M440TB/G P440TB/G
12 24 36 42
630 630 630 630
1250 1250 1250 1250
Conductor sizes (mm2) min
max
185 185 185 185
630 630 630 630
05/2017
KIT CONTENTS The complete (K)(M)(P)440TB/G tee connector kit comprises the following components:
The kit also comprises silicone grease, field control mastic, installation instructions and crimp chart.
Conductor contact TMBC-X
Connector housing (K)(M)(P)440BT/G
Clamping screw 400TCS
ORDERING INSTRUCTIONS To order the tee connector, select the ordering part number which gives you the best centring of your core insulation diameter and substitute X using table X, according to your conductor size and type. Add a 'K' for use up to 24 kV, add an 'M' for use up to 36 kV, add a 'P' for use up to 42 kV. EXAMPLE: The copper wire screened cable is 36 kV, 240 mm2 stranded aluminium with a diameter over core insulation of 37.0 mm. Order a M440TB/G-32-240(K) M-12-2 tee connector kit.
For use with copper tape screened cables.
Order: Kit MT.
For use with other cable types.
Please contact our representative.
(K)(M)(P)440TB/G-W-X connector kit
Basic insulating plug (K)(M)(P)400BIPA + rubber cap
Conductor contact TBC-X
Cable reducer 611CA-W
TABLE W Dia. over core insulation (mm)
Ordering part number 440TB/G-22-X 440TB/G-27-X 440TB/G-32-X 440TB/G-37-X 440TB/G-43-X
min
max
23.5 28.5 34.0 39.0 45.5
31.0 37.5 42.5 48.5 56.0
TABLE X Conductor sizes (mm2)
Aluminium conductor
Aluminium and copper conductor
Copper conductor
Bolted
DIN hexagonal
DIN hexagonal
Deep indent
185
185(K)M-12-2
185KM-12-1
185(K)M-11-2
240
240(K)M-12-2
240KM-12-1
240(K)M-11-2
300
300(K)M-12-2
300KM-12-1
300(K)M-11-2
400
400(K)M-12-2
400KM-12-1
400(K)M-11-2
500
500(K)M-12-2
500KM-12-1
500(K)M-11-2
630
–
630KM-12-1
630(K)M-11-2
For applications outdoors and in humid climate.
Order: +MWS.
For use in potentially explosive atmospheres (for 12 kV max).
Add -/ATEX to part number.
Components can be ordered individually.
When installed on an appropriate equipment bushing:
1250 A continuously
9
440PB
COUPLING CONNECTOR FOR 400TB AND 440TB
APPLICATION
TECHNICAL CHARACTERISTICS
Separable coupling connector (bolted type) for dual cable arrangement. It has been designed to be used with 400TB and 440TB separable tee connector.
• A thick conductive EPDM jacket provides a total safe to touch screen. • Each separable connector is tested for AC withstand and partial discharge prior to leaving the factory.
DESIGN
410 mm
1. Interface designed to fit 400TB/440TB connector. 2. Bus for 440PB. 3. Conductive EPDM insert. 4. Insulating EPDM layer moulded between the insert and the jacket. 5. Conductive EPDM jacket. 6. Conductive EPDM cap. 7. Basic insulating plug. 8. Conductor connector (hexagonal crimping, deep indent crimping or bolted). 9. Cable reducer. 10. Earthing lead. 11. Threaded M16 stud for the equipment bushing.
11
2
6
8
1 400TB or 440TB connector
7
3
440PB coupling connector
4
355 mm
5
10
9
6/10 (12) kV 6.35/11 (12) kV 8.7/15 (17.5) kV 12/20 (24) kV 12.7/22 (24) kV 18/30 (36) kV 19/33 (36) kV 20.8/36 (42) kV Up to 42 kV 800 A
155 mm
The screen break design enables cable outer sheath testing without removing or dismantling the connector.
SPECIFICATIONS AND STANDARDS The 440PB coupling connector meets the requirements of CENELEC HD 629.1. Separable connector type
Voltage Um (kV)
Current Ir (A)
440PB/G K440PB/G M440PB/G P440PB/G
12 24 36 42
800 800 800 800
Conductor sizes (mm2) min
max
185 185 185 185
630 630 630 630 05/2017
10
KIT CONTENTS
The kit also comprises silicone grease, field control mastic, installation rod, installation instructions and crimp chart.
The complete (K)(M)(P)440PB/G coupling connector kit comprises 3 x the following components:
Conductor contact TMBC-X
Contact rod 440PB-CR + M16 stud
Connector housing (K)(M)(P)440BP/G
ORDERING INSTRUCTIONS To order the coupling connector, select the ordering part number which gives you the best centring of your core insulation diameter and substitute X using table X, according to your conductor size and type. Add a 'K' for use up to 24 kV, add an 'M' for use up to 36 kV, add a 'P' for use up to 42 kV. EXAMPLE: The copper wire screened cable is 36 kV, 240 mm2 stranded aluminium with a diameter over core insulation of 37.0 mm. Order 3 x M440PB/G-32-240(K) M-12-2 coupling connector kit.
For use with copper tape screened cables.
Order: Kit MT.
For use with fabric tape (graphite) screened cables.
Order additional semi-conductive tape (type TSC).
3 x (K)(M)(P)440PB/G-W-X coupling connector kit
Conductor contact TBC-X
Cable reducer 611CA-W
TABLE W Dia. over core insulation (mm)
Ordering part number 3 x 440PB/G-22-X 3 x 440PB/G-27-X 3 x 440PB/G-32-X 3 x 440PB/G-37-X 3 x 440PB/G-43-X
min
max
23.5 28.5 34.0 39.0 45.5
31.0 37.5 42.5 48.5 56.0
TABLE X
Conductor sizes (mm2)
Aluminium conductor
Aluminium and copper conductor
Copper conductor
Bolted
DIN hexagonal
DIN hexagonal
Deep indent
185
185(K)M-12-2
185KM-12-1
185(K)M-11-2
240
240(K)M-12-2
240KM-12-1
240(K)M-11-2
300
300(K)M-12-2
300KM-12-1
300(K)M-11-2
400
400(K)M-12-2
400KM-12-1
400(K)M-11-2
500
500(K)M-12-2
500KM-12-1
500(K)M-11-2
630
–
630KM-12-1
630(K)M-11-2
For use with easy strip semi-conductive screened cables. Order:
Field control mastic (type MFC).
For use with copper wire screened cables.
No earthing device is necessary.
For use with other cable types.
Please contact our representative.
For outdoor applications.
Order: +MWS.
11
400PB-10SA
INTERFACE C SURGE ARRESTER
APPLICATION
TECHNICAL CHARACTERISTICS
Surge arrester designed to protect medium voltage components, including transformers, equipment, cable and accessories from high voltage surges resulting from lightning or switching.
• This surge arrester is a metal oxide varistor surge arrester in an elbow configuration. • Each arrester is tested for AC withstand, partial discharge and critical voltage prior to leaving the factory.
DESIGN Surge arrester comprising: 1. Conductive EPDM insert. 2. Conductive EPDM jacket. 3. Insulating EPDM layer moulded between the insert and the jacket. 4. Contact rod. 5. Earthing lead. 6. Earth connection. 7. Steel cap. 8. Metal oxide valve elements. 9. Type C - 630 A interface as described by CENELEC EN 50180 and 50181.
247 mm 145 mm
Dia. 80 mm
4 1
5
3
L2 L1
8
Up to 42 kV
Dia. 70 mm
SPECIFICATIONS AND STANDARDS
7 6
The 400PB-10SA surge arresters meet the test requirements of IEC 60099-4.
12
9
2
6/10 (12) kV 6.35/11 (12) kV 8.7/15 (17.5) kV 12/20 (24) kV 12.7/22 (24) kV 18/30 (36) kV 19/33 (36) kV 20.8/36 (42) kV
Surge arrester type
Nominal discharge current In (kA)
Rated voltage Ur (kV)
Max. continuous operating voltage Uc (kV)
L1
L2
400PB-10SA-15L 400PB-10SA-18L 400PB-10SA-22L 400PB-10SA-24L 400PB-10SA-30L 400PB-10SA-6N 400PB-10SA-9N 400PB-10SA-12N 400PB-10SA-15N 400PB-10SA-18N 400PB-10SA-22N 400PB-10SA-24N 400PB-10SA-30N 400PB-10SA-33N 400PB-10SA-36N 400PB-10SA-45N 400PB-10SA-51N
10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
15 18 22 24 30 6 9 12 15 18 22 24 30 33 36 45 51
12.0 14.4 17.6 19.2 24.0 4.8 7.2 9.6 12.0 14.4 17.6 19.2 24.0 26.4 28.8 36.0 40.8
270 270 370 370 370 270 270 270 270 270 270 370 370 370 370 470 470
310 310 410 410 410 310 310 310 310 310 310 410 410 410 410 510 510
Dimensions (mm)
05/2017
TYPICAL APPLICATIONS AND DIMENSIONS
ORDERING INSTRUCTIONS
To order the surge arrester, specify the surge arrester type, as described on previous page.
410 mm 220 mm
185 mm
Type 400TB or 440TB tee connector
EXAMPLE: For a maximum continuous operating voltage (r.m.s.) of 24 kV and a nominal discharge current of 10 kA. Order a 400PB-10SA-30N surge arrester.
Type 400PB-10SA surge arrester
Note: the surge arrester body needs to be positioned vertically after installation.
TECHNICAL DATA Surge arrester type
Steep current residual voltage @ 10 kA [1/20 µs] (kV)
400PB-10SA-15L 400PB-10SA-18L 400PB-10SA-22L 400PB-10SA-24L 400PB-10SA-30L 400PB-10SA-6N 400PB-10SA-9N 400PB-10SA-12N 400PB-10SA-15N 400PB-10SA-18N 400PB-10SA-22N 400PB-10SA-24N 400PB-10SA-30N 400PB-10SA-33N 400PB-10SA-36N 400PB-10SA-45N 400PB-10SA-51N
47.1 56.5 69.2 75.2 94.0 20.4 28.5 38.0 48.1 58.1 70.1 77.0 97.0 103.4 115.9 144.1 166.0
Lightning current residual voltage [8/20 µs] (kV)
Switching impulse residual voltage [36/90 µs] (kV)
@ 5 kA
@ 10 kA
@ 20 kA
@ 125 A
@ 500 A
38.9 46.7 57.1 62.1 77.6 16.8 23.5 31.4 39.7 48.0 57.9 63.6 80.1 85.4 95.7 119.0 137.1
42.3 50.8 62.2 67.6 84.5 18.3 25.6 34.2 43.2 52.2 63.0 69.2 87.2 93.0 104.2 129.5 149.2
47.4 56.9 69.7 75.8 94.7 20.5 28.7 38.3 48.4 58.5 70.6 77.6 97.7 104.2 116.8 145.1 167.2
29.8 35.8 43.8 47.7 59.6 12.9 18.0 24.1 30.5 36.8 44.4 48.8 61.5 65.6 73.5 91.3 105.2
31.8 38.2 46.7 50.8 63.5 13.7 19.2 25.7 32.5 39.2 47.3 52.0 65.5 69.9 78.3 97.3 112.1
High current impulse withstand (kA) 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
13
400TR AND 400TR-LB APPLICATION • The test rod can be used for: - cable fault location - cable testing - phasing checks, etc. • Connections may be made with a cable lug, a 4 mm plug or spring clips.
TECHNICAL CHARACTERISTICS • The 400TR test rod can be used with 400TE, 400TB and 440TB connectors. • The 400TR-LB is for use with the 400LB connector.
DESIGN
400TR
1. Insulating shroud. 2. Threaded rod for test connection. 3. Two nuts M12. 4. Insulation. 5. Copper test rod stem. 6. Wing nut. An insulating shroud is provided to allow the application of test voltages when bushings are closely spaced.
TEST RODS
400TR-LB
1 M10
1
2 M12
3
INSTALLATION
60
6
2 40
480
The test rod is mounted on to the clamping screw in the type C interface tee and coupling connectors. The test cable is connected to the threaded stem and the insulating shroud moved to its final position over the end of the test rod.
465
4
4
310
288
Dia. 25
5
ORDERING INSTRUCTIONS
5
Simply specify: 400TR or 400TR-LB test rod.
In mm.
14
Test rod type
Maximum A.C. test voltage (50 Hz - 1 min)
Maximum D.C. test voltage (8 x U0 - 30 min)
Impulse voltage (1.2 x 50 µs) min
400TR 400TR-LB
36 kV 36 kV
96 kV 96 kV
95 kV 95 kV
05/2017
INSTALLATION TOOL
400TK AND 400SW
APPLICATION • The box spanner and box spanner key are designed to facilitate assembly of 400TE, 400TB and 440TB connectors. • The 400TK box spanner is used to install the 400TEF clamping pin contact or 400TCS clamping screw. • The 400SW box spanner key fits on the hex nut of the 400BIPA basic insulating plug.
400SW 400TK
ORDERING INSTRUCTIONS Simply specify: - 400TK box spanner - 400SW box spanner key.
15 05/2017
15
ACCESSORIES APPLICATION For use with connectors and bushings with an interface C as described by CENELEC EN 50180 and 50181.
TECHNICAL CHARACTERISTICS All these products, except the earthing plugs, are tested for AC withstand and partial discharge prior to leaving the factory.
6/10 (12) kV 6.35/11 (12) kV 8.7/15 (17.5) kV 12/20 (24) kV 12.7/22 (24) kV 18/30 (36) kV 19/33 (36) kV 20.8/36 (42) kV Up to 36 kV
400DR-B/G DEAD-END RECEPTACLE Fits over a bushing with a type C interface to provide 'dead-end' facility. The dead-end receptacle is supplied with an earth lead.
400SOP-B STAND-OFF PLUG Is designed to support and 'deadend' connectors with a type C interface when removed from equipment.
400GP-B EARTHING PLUG Is designed to support and earth connectors with a type C interface when removed from equipment.
ORDERING INSTRUCTIONS Order 400DR-B/G for 12 kV, K400DR-B/G for 24 kV or M400DR-B/G for 36 kV applications.
ORDERING INSTRUCTIONS Order 400SOP-B for 12 kV, K400SOP-B for 24 kV, M400SOP-B for 36 kV or P400SOP-B for 42 kV applications.
ORDERING INSTRUCTIONS Order 400GP-B for 12, 24, 36 or 42 kV applications.
05/2017
16
400BIPA BASIC INSULATING PLUG Acts as a tightening nut for the 400TB and 440TB tee connector kits. The plug contains a voltage detection point. The conductive rubber protection cap is included.
400CP-SC CONNECTING PLUG For connecting two or more connectors with a type C interface together, thus creating a separable cable joint or a multiple cable connection to equipment.
440CP CONNECTING PLUG For connecting two or more 440TB connectors, thus creating a separable cable joint or a multiple cable connection to equipment. For use up to 1250 A. Only for use with 440TB.
400RTPA REDUCING TAP PLUG Provides a type A interface to connectors with a type C interface. A 'C' spanner, 600SW, is used to tighten the reducing tap plug on to its mating part.
KIT MT EARTHING KIT FOR COPPER TAPE SCREENED CABLES Contains a tinned copper braid (25 mm² - L = 500 mm), a tinned copper wire for cleating and some water sealing mastic.
400BE/G BUSHING EXTENDER Provides an extension piece to allow cables to stand away from equipment. Is used in conjunction with the 400CP, 440CP or 440PB. The bushing extender is supplied with an earth lead.
ORDERING INSTRUCTIONS Order 400BIPA for 12 kV, K400BIPA for 24 kV M400BIPA for 36 kV or P400BIPA for 42 kV applications.
ORDERING INSTRUCTIONS Order 400CP-SC for 12 kV, K400CP-SC for 24 kV or M400CP-SC for 36 kV applications.
ORDERING INSTRUCTIONS Order 440CP for 12 kV, K440CP for 24 kV or M440CP for 36 kV applications. Order (K)(M)440CP + 676SA for connection to an already installed 440TB connector.
ORDERING INSTRUCTIONS Order 400RTPA for 12 kV or K400RTPA for 24 kV applications. Order 600SW for the 'C' spanner.
ORDERING INSTRUCTIONS Order Kit MT for 12 kV, 24 kV 36 kV or 42 kV applications.
ORDERING INSTRUCTIONS Order 400BE/G for 12 kV, K400BE/G for 24 kV, M400BE/G for 36 kV or P400BE/G for 42 kV applications.
17
POSSIBLE ARRANGEMENTS 400TB/G-P2
400TB/G
Dual cable arrangement. Order 400TB/G-P2 for 12 kV, K400TB/G-P2 for 24 kV or M400TB/G-P2 for 36 kV applications.
Single cable arrangement. Order 400TB/G for 12 kV, K400TB/G for 24 kV, M400TB/G for 36 kV or P400TB/G for 42 kV applications.
250
500
basic insulating plug tee connector
110
connecting plug
110
basic insulating plug
245
400TB/G-L2
400BE+440PB
2-way connection. Order 400TB/G-L2 for 12 kV, K400TB/G-L2 for 24 kV or M400TB/G-L2 for 36 kV applications.
Connector standing away from equipment. Order 400BE+440PB for 12 kV, K400BE+440PB for 24 kV, M400BE+440PB for 36 kV or P400BE+440PB for 42 kV applications. 410
400BE bushing extender 400
265
In mm. 05/2017
18
400TB/G-L3 3-way connection. Order 400TB/G-L3 for 12 kV, K400TB/G-L3 for 24 kV or M400TB/G-L3 for 36 kV applications.
400TB/G-L4 Disconnectable tap-off. Order 400TB/G-L4 for 12 kV, K400TB/G-L4 for 24 kV or M400TB/G-L4 for 36 kV applications.
400TB/G-L5
505
2-way connection with tap-off. Order 400TB/G-L5 for 12 kV or K400TB/G-L5 for 24 kV applications.
In mm.
19
440TB+440PB-P2 Dual cable arrangement. Order 440TB/G+440PB/G-P2 for 12 kV, K400TB/G+K440PB/G-P2 for 24 kV, M400TB/G+M440PB/ G-P2 for 36 kV, P400TB/ G+P440PB/G-P2 for 41,5 kV.
410
400
155
CONNECTOR ON STANDOFF PLUG
CONNECTOR ON EARTHING PLUG
Order 400SOP-B for 12 kV, K400SOP-B for 24 kV or M400SOP-B for 36 kV applications.
Order 400GP-B for 12 kV, 24 kV and 36 kV applications.
400BIPA basic insulating plug stand-off plug
400TB/G tee connector
CABLE AND EQUIPMENT TESTING
20 In mm. 05/2017
Nexans Network Solutions N.V. - Div. Euromold Zuid III, Industrielaan 12, B-9320 Erembodegem Tel.: +32(0)53 85 02 11 •
[email protected] • www.euromold.be
Find out more about Nexans Power Accessories.
05/2017